2200VA/1700W - 11 Minute Full Load - 6 x NEMA 5-15R - MPN: SMART2200NET See Product Details
Description
UPS System with six outlets protects network servers against damage and downtime due to blackouts, brownouts, overvoltages and surges. Advanced automatic voltage regulation keeps servers productive through brownouts and overvoltages without using battery power. Up to three built-in communication ports and intelligent operation provide advanced power monitoring and control when used with included PowerAlert Software.
Quick Glance
Power Rating: 2.20 kVA/1.70 kW
Surge Suppression: 480 J
Input Connectors: 3 x DB-9, 6 x NEMA 5-15R, NEMA 5-15P
Connectors
Input Connectors: 3 x DB-9, 6 x NEMA 5-15R, NEMA 5-15P
Battery
Uptime Full Load: 11 Min
Battery Replaceability: Factory Replaceable
Power
Power Rating: 2.20 kVA/1.70 kW
Output Waveform: Pulse-width Modulated Sine Wave
Power Rating Watts: 1700 W
Power Rating VA kVA: 2200 VA
Input Voltage Supported: 110 V AC
Max Surge Energy Rating: 480 J
General
Category: UPS
Backup/Run Time: 0.18 Hour 2.20 kW Full Load, 0.45 Hour 1.10 kW Half Load
Class: Power Equipment
Dimensions: 17" Height x 9" Width x 12.50" Depth
Weight: 80 lbs
Warranty Information: 2 Year
URL: Manufacturer Link
Additional Specifications
Frequency Band: SMART2200NET line interactive UPS offers battery derived AC output during power outages, voltage regulation during brownouts and overvoltages, plus network-grade AC surge suppression 2200VA / 1700 watt power handling capability supports a variety of networking, telecom and other sensitive electronic devices Large internal batteries offer runtimes of 27 minutes at half load (1100VA / 850 watts) and 11 minutes at full load (2200VA / 1700 watts) Runtime is further expandable with optional external BP24V33 battery packs (output VA is de-rated as external battery packs are added, see specifications) Automatic Voltage Regulation (AVR) circuits maintain 120V nominal output over an input voltage range of 87-140V Includes 6 fully protected NEMA 5-15R outlets with 2 single outlet load banks that can be individually powered off and back on again via software interface PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, pager & email notification, event logging and running user defined script commands Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces, or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software In addition to the contact closure monitoring of on battery, low battery and power restored messaging, built-in RS-232 interface supports messaging of UPS and line power status, including AC line voltage, DC battery voltage and remaining battery capacity Supports activate self-test and UPS output power control for scheduled or immediate reboot of connected equipment Diagnostic LEDs (indicate 17 performance conditions) UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Business) Listed $250,000 Ultimate Lifetime Insurance (USA & Canada Only)
Battery Recharge Time: 4 Hour
Software Included: PowerAlert Software
Output Voltage: 120 V AC Single-phase
Filtering: EMI/RFI
Humidity: 0 to 95% Non-condensing Relative Humidity
Modular Slots: 3 x Communications Slot
Network Management: SNMP Manageable Optional
Overload Protection: 20A input breaker
Switching Time: 4 ms
Temperature: 5F (-15C) to 122F (50C) Storage
Alarm: On Battery